This 2017 Generator set has only 46.6 hrs from new. 450KVA Standby, 409kVA Prime 3 Phase 50HZ. S/N L17H008057
QSX15G8 Diesel engine, Enclosed, Emergency Standby Power (ESP), Emissions Level : EPA Tier 2, Local Codes and/or Regulation : CE, AS3000 Compatible. Output Voltage : 416/240, 3 Phase, Wye, 4 Wire
Engine QSX15G8, Engine Air Cleaner - Duty Rating : Normal Duty
Engine Coolant Heater : 240V. Main Generator HC5C, 12 Leads, 50 Hertz (Hz), 190 - 220V and 380 - 440V, 16
3C, Emergency Standby Power (ESP). Generator Accessories, Voltage Regulator - PMG
Main Generator Heater : None Supplied. Genset Housing Sound Attenuated, Steel, Munsell Green
Exhaust System, Silencer Grade : Enclosure Critical
Cooling System; Genset Mounted Radiator, 50C / 122F, Genset Mounted. Engine Coolant Mixture : 50% Antifreeze, 50% Water
Primary Electrical Isolation Device
One Circuit Breaker
Primary Electrical Isolation Device
630A, 690V IEC, 600V UL, 4 Pole, 100%, Left Facing
Primary Electrical Isolation Device Accessories
Shunt Trip - 24VDC
Control System Options
PowerCommand 2.2
Control Panel Mounting (Viewed From Generator End) : Left Facing
Control Language : English
Warning - Low Battery Voltage
Shutdown - Low Coolant Level
Display - Control LCD
Control Cabinet Heater : None Supplied
Starting Batteries
Lead Acid Batteries - Wet
Battery Charger
Set Mounted, 5A, 240V
Fuel Tank;
In Skid, Dual Wall, 711 Litres / 188 US Gallons, With Spilla
ge Catchment
Fuel Tank Accessories
Fuel Level Alarms : None Supplied
Genset Testing : Current load test Report
Warranty
As is fit for purpose.